Bulletin: SVB-120
Date Issued: July 14, 2006
Category: Design Improvement
Subject: Operating System Modification
Machine Models: Bundle Breakers¨ delivered since Sept. 2002
Back to Index
Problem:
A customer
reported that their Bundle Breaker ¨
overheated and damaged the hydraulic pump while the machine was left
unattended and in automatic operation. This unit had been in service
since 2002.
The Bundle
Breaker ¨
control system is intended to shut down the machine as a protective
measure if 999 continuous seconds of inactivity have been
experienced while operating in the automatic mode. However, on-site
investigation by Alliance revealed that the automatic shutdown
feature in the delivered control program logic did not function as
intended and led to overheating of the hydraulic system.
In response to
this problem an Alliance technician modified the control program and
confirmed proper operation of the automatic shutdown feature. This
control system logic change has also been accomplished for all new
and future production Bundle Breaker ¨
units.
Back to top
Recommended
action:
Alliance
recommends that Bundle Breaker ¨
customers perform the following modification within 30 days after
receipt of this service bulletin.
Back to top
Modification Procedure:
If you need
additional assistance to perform this modification or have any
questions, please call Mr. Gary Kneale of Alliance Field Service at
(509) 842-5134 for further information.
-
Upload the Bundle Breaker ¨
operating program in the machine PLC to a laptop. Using RS Logix
open the program for editing.
-
Refer to Figure 1 which has been extracted from Ladder 3 in
the Operating Program portion of the Maintenance Manual
documentation. Make the following control system logic changes (as
highlighted) –
Figure 2 shows
the corrected configuration for Rung 9.
-
Save the
edited program. Download the program back into the Bundle Breaker ¨
and save to EEPROM.
-
Check for normal Bundle Breaker ¨
operation.
-
In Automatic operation verify that the Bundle Breaker ¨
shuts down after approx 16.5 minutes of inactivity.
|

Figure 1. Ladder 3 Rungs 9 & 10 prior to change (as
delivered) |
|

Figure 2. Ladder 3 Rung 9 corrected configuration |